Electrical
Specification | Rating |
Power requirements |
Input: 10 – 28V DC 30 mA @ 24 VDC - With no field device attached. 52 mA @ 24 VDC - With a field device at 22mA. 50 mA @ 12 VDC - With no field device attached. 72 mA @ 12 VDC - With a field device at 22mA. |
Power consumption |
0.8 W - With no field device attached. 1.4 W - With a field device at 22mA. 1.7 W - With input channel shorted (IP Point HART In) |
Connector (Power) | Binder M12-A, 5 contact, cable outlet: 4-6 mm, female cable connector, plastic lock, screw terminal connection. (Part Number: 99 0436 10 05) |
Connector (Ethernet) | Binder M12-D, 4 contact, cable outlet: 6 - 8 mm, shieldable, CAT 5 screw terminal connection, static ring version (Part number : 99 3729 810 04) |
Conductors | 20 AWG (Red, Black, Green) |
Enclosure rating | IP66 |
Temperature | -20 – 70 °C |
Emissions | IEC61000-6-4 |
ESD Immunity | EN 61000-4-2 |
Radiated RF Immunity | IEC 61000-4-3 |
EFT/B Immunity | EFT: IEC 61000-4-4 |
Surge Immunity | Surge: IEC 61000-4-5 |
Conducted RF Immunity | IEC 61000-4-6 |