ControlNet, Rockwell, Allen-Bradley, EtherNet/IP, MicroLogix, SLC, DH485, Bridge, Gateway, 1756, 1769, PanelView, PanelView Plus, PV800, PLC5, Mapping, Tags, Direct-to-Tag, ControlNet Router
CONTROLNET ROUTER
A-CNR
The ControlNetRouter provides an efficient method of bridging ControlNet and Ethernet networks.
-
- The module has the following ControlNet operating modes:
- ControlNet Target, where the ControlNet Router can be owned by a controller over scheduled ControlNet.
- ControlNet Originator, where the ControlNet Router owns ControlNet IO over a scheduled ControlNet connection.
- The module has the following Ethernet operating modes:
- PCCC Client, allowing the ControlNet Router to emulate a PLC5 or SLC to exchange data with Ethernet-only PanelViews.
- EtherNet/IP Target, where the ControlNet Router can be owned by a controller via a Class 1 EtherNet/IP connection.
- EtherNet/IP Originator, where the ControlNet Router owns EtherNet/IP IO using a Class 1 EtherNet/IP connection.
- Modbus TCP Master, where the ControlNet Router module can exchange data with Modbus TCP Slaves.
- Modbus TCP Slave, where the ControlNet Router module can exchange data with a Modbus TCP Master.
- The ControlNet network can be scheduled using the Slate software environment.
- ControlNet Router can operate as ControlNet Keeper.
- Multiple ControlNet Routers can own ControlNet IO on the ControlNet network.
- Supports Redundant ControlNet.
- Supports Promiscuous Capture mode allowing the ControlNet Router to capture all traffic on the ControlNet network.
- Supports unscheduled ControlNet allowing Logix programming over ControlNet.
- Dual Ethernet ports which supports Device-Level-Ring (DLR).
- Network Time Protocol (NTP) supported for external time synchronization.
- ControlNet, EtherNet/IP, and Modbus Statistics and packet captures providing diagnostic data for fault finding.
- Built-in webserver providing (read-only) diagnostics.
- Small form factor – DIN rail mounted.
- The module has the following ControlNet operating modes:

Overview
The ControlNet Router provides intelligent data routing between either EtherNet/IP or Modbus TCP/RTU and a ControlNet network. This allows the user to integrate ControlNet devices into a EtherNet/IP based Rockwell Logix platform (e.g., ControlLogix or CompactLogix) or any Modbus Master or Slave device with minimal effort.
The ControlNet Router also provides intelligent data routing between ControlNet and Ethernet PCCC (CSP). This will allow the user to connect new PanelView Plus devices (with no ControlNet interface) to existing ControlNet networks.
The ControlNet Mode can be configured to be either of the following two interface modes:
Target
A Logix controller can own the ControlNet Router over ControlNet using a scheduled ControlNet connection when the ControlNet Router is operating as a ControlNet target. This will allow the ControlNet Router to exchange data with the Logix controller using the input and output assembly of the scheduled ControlNet connection. Data from EtherNet/IP or Modbus TCP devices can be mapped to the Logix controller over ControlNet.
Originator
As a ControlNet originator, the module can use one of two methods to read and write data to and from ControlNet IO:
- Scheduled ControlNet
The ControlNet Router can be configured to own ControlNet IO by using the Slate software to configure the IO connections and schedule the ControlNet network. Data from the ControlNet IO (via the IO input and output assemblies) can be exchanged with any of the Ethernet mode interfaces (e.g. EtherNet/IP Target or Modbus TCP Slave).
- ControlNet Explicit Messaging
This allows the ControlNet Router to exchange data with up to 10 ControlNet devices using explicit messaging over ControlNet. The module can Get or Set data in the remote ControlNet devices with Custom Class, Instance, Attribute values.
The Ethernet Mode can be configure to be any of the following five interface modes:
PCCC Client
The support for Ethernet PCCC (CSP) allows the module to emulate a PLC5 or SLC providing a legacy interface for PanelViews and other devices over scheduled ControlNet. This will allow an Ethernet-only PanelView to exchange data with a Logix controller using an existing ControlNet connection.
EtherNet/IP Target
A Logix controller can own the ControlNet Router over EtherNet/IP using a class 1 connection when the ControlNet Router is operating as a EtherNet/IP Target. This will allow the ControlNet Router to exchange data with the Logix controller using the input and output assembly of the EtherNet/IP Class 1 connection. Data from ControlNet devices (when operating as a ControlNet Originator) or Controllers on ControlNet (when operating as a ControlNet Target) can be mapped to the Logix controller over EtherNet/IP.
EtherNet/IP Originator
As an EtherNet/IP originator, the module can use one of three methods to read and write data to and from the EtherNet/IP network:
- EtherNet/IP Class 1 Connection
The ControlNet Router can be configured to own EtherNet/IP IO by using the Slate software to configure the Class 1 connections. Each ControlNet Router can own up to 10 EtherNet/IP devices. Data from the EtherNet/IP IO (via the input and output assemblies) can be exchanged with the ControlNet network (when operating as either a ControlNet Target or Originator).
- EtherNet/IP Explicit Messaging
This allows the ControlNet Router to exchange data with up to 10 EtherNet/IP devices using explicit messaging over EtherNet/IP. The module can use either Class 3, Unconnected Messaging (UCMM), or Logix Tag to Get and Set data in the remote EtherNet/IP devices with configurable Class, Instance, Attribute values (when using UCMM or Class 3). Logix Tag messages are used to exchange data with a Logix controller by directly writing to or reading from Logix tags. The user can browse to the Logix controller (using the Slate Target Browser) as well as browse the Logix Controller Tag list (using the Slate Tag Browser) to select the desired destination Tag.
Modbus TCP Master
The data from either ControlNet IO (when operating as a ControlNet originator) or ControlNet input and output assemblies (when operating as a ControlNet Target) will be written to, or read from, the module’s internal Modbus Registers. The Modbus Auxiliary Map can then be used to configure the Modbus data exchange between multiple remote Modbus Slave devices and the module’s internal Modbus registers. The Modbus communication utilizes Modbus TCP.
Modbus TCP Slave
The data from either ControlNet IO (when operating as a ControlNet originator) or ControlNet input and output assemblies (when operating as a ControlNet Target) will be written to, or read from, the module’s internal Modbus Registers using the internal mapping functions. These Modbus registers can be accessed by a remote Modbus Master using Modbus TCP.
The ControlNet Router uses an internal mapping strategy allowing the user to map any data from any supported interface to any other supported interface. Slate provides an online import tool for existing Logix controllers with IO connections to assist with the setup and configure of originator connections (EtherNet/IP or ControlNet).
The ControlNet Router can also be used to go online and program a Logix controller over ControlNet using an Ethernet connection from the local PC.
Application
Typical Setup for Ethernet only PanelViews:
Example of a typical network setup in PLC Emulation mode:
Example of PLC5/SLC500 Messaging in PLC Emulation Mode:
Typical Setup for EtherNet/IP Target to ControlNet IO:
Typical Setup for Modbus TCP Slave to ControlNet IO:
Typical Setup for ControlNet Target to EtherNet/IP IO:
Typical Setup for ControlNet Target to Modbus TCP Slaves:
Specification
Electrical
Specification | Rating |
Power requirements | Input: 10 – 36V DC, (85 mA @ 24 VDC) |
Power consumption | 2 W |
Connector | 3-way terminal |
Conductors | 24 – 18 AWG |
Enclosure rating | IP20, NEMA/UL Open Type |
Temperature | -20 – 70 °C |
Earth connection | Yes, terminal based |
Emissions | IEC61000-6-4 |
ESD Immunity | EN 61000-4-2 |
Radiated RF Immunity | IEC 61000-4-3 |
EFT/B Immunity | EFT: IEC 61000-4-4 |
Surge Immunity | Surge: IEC 61000-4-5 |
Conducted RF Immunity | IEC 61000-4-6 |
ControlNet
Specification | Rating |
Connectors | 2 x BNC connectors (ControlNet A and B) |
Conductors | Quad shield RG-6 coaxial cable |
Routing Supported (RSLogix programming) | Yes |
Redundant ControlNet | Supported |
ControlNet Target
Specification | Rating |
Scheduled Connection Size |
Max Input Size – 408 bytes (400 bytes mapped data) Max Output Size – 404 bytes (400 bytes mapped data) |
Unscheduled Routed Client Max | 40 |
Scheduled Connection Count | 1 |
ControlNet Originator
Specification | Rating |
Scheduled Connection Max Count | 10 |
Scheduled Connection Max Data |
Input Connection Data 500 bytes per connection Output Connection Data Total of 277 bytes for 1 connection. Total of 269 bytes for 2 connections. Total of 261 bytes for 3 connections. Total of 253 bytes for 4 connections. Total of 245 bytes for 5 connections. Total of 237 bytes for 6 connections. Total of 229 bytes for 7 connections. Total of 221 bytes for 8 connections. Total of 213 bytes for 9 connections. Total of 205 bytes for 10 connections. |
Explicit Unscheduled Connection Max | 10 |
Multiple ControlNet Router Connection Originators | Supported |
PCCC
Specification | Rating |
Max PCCC Connections | 10 |
Max PCCC Payload | 1000 bytes |
EtherNet/IP Target
Specification | Rating |
Class 1 Connection Size |
Max Input Size – 500 bytes (492 bytes mapped data) Max Output Size – 496 bytes (492 bytes mapped data) |
Class 1 Connection Count | 1 |
Class 3 Messaging Supported | Yes |
UCMM Messaging Supported | Yes |
EtherNet/IP Originator
Specification | Rating |
Class 1 Cyclic Connections Supported | Yes |
Class 3 / UCMM Connections Supported | Yes |
Class 1 Connection Count | 10 |
Class 3 / UCMM Target Device Count | 10 |
Class 3 / UCMM Mapping Count | 50 |
Direct-To-Tag Logix Support | Yes |
Modbus TCP Master
Specification | Rating |
Modes Supported | Modbus TCP |
Max Modbus Slave device | 20 |
Max Modbus Mapping | 100 |
Mapping Ranges |
Holding Register 0 – 65535 Input Register 0 – 65535 Input Status 0 – 65535 Coil Status 0 – 65535 |
Base Offset |
Modbus (Base 0) PLC (Base 1) |
Configurable Modbus TCP Port | Yes |
Data Re-formatting Supported |
BB AA BB AA DD CC CC DD AA BB DD CC BB AA |
Modbus TCP Slave
Specification | Rating |
Modes Supported | Modbus TCP |
Mapping Ranges |
Holding Register 0 – 65535 Input Register 0 – 65535 Input Status 0 – 65535 Coil Status 0 – 65535 |
Base Offset |
Modbus (Base 0) PLC (Base 1)
|
Configurable Modbus TCP Port | Yes |
Ethernet
Specification | Rating |
Connector | RJ45 |
Conductors | CAT5 STP/UTP |
ARP connections | Max 40 |
TCP connections | Max 40 |
CIP connections | Max 10 |
Communication rate | 10/100Mbps |
Duplex mode | Full/Half |
Auto-MDIX support | Yes |
Controller Support | ControlLogix, CompactLogix, MicroLogix, SLC |
Embedded Switch | Yes, 2 x Ethernet ports |
Certifications
Specification | Rating |
CE Mark | ![]() |
UL Listed FILE: E494895 |
CLASS 1, DIV 2, GROUPS A, B, C, D
|
ODVA Conformance | ![]() |
RoHS3 Compliant | ![]() |
Dimensions
Downloads
Documents






Examples




EDS Files

Firmware



